Buildings & data centers

Water-cooled centrifugal chiller

Cooling is a heat pump with a known ceiling. Everything under it is waste.

A chiller moves heat from chilled water to condenser water. The temperature gap between them sets the work. Fouled tubes and warm condenser water widen the gap, and the compressor pays.

500 tons, R-134a, 44 °F leaving chilled water

Sketch of a water-cooled centrifugal chiller: evaporator, centrifugal compressor, condenser and expansion valve, with chilled water and condenser water loops and numbered sensor points.12345678chilled watercondenser water
Full load
0.583 kW/ton
IPLV
0.405 kW/ton
Capacity
500 tons
Second-law efficiency
70%

Anatomy and nameplate

Sketch of a water-cooled centrifugal chiller: evaporator, centrifugal compressor, condenser and expansion valve, with chilled water and condenser water loops and numbered sensor points.12345678chilled watercondenser water
  1. 1Chilled water supply and return temperature. Sets load with the flow reading.
  2. 2Chilled water flow. Cooling delivered in tons.
  3. 3Evaporator pressure. Gives the saturated refrigerant temperature.
  4. 4Condenser pressure. Gives the condensing temperature and the approach.
  5. 5Condenser water temperatures and flow. Tower side of the lift.
  6. 6Compressor current. Input power.
  7. 7Compressor vibration. Bearing and gear condition.
  8. 8Oil pressure and temperature. Lubrication health.
Water-cooled centrifugal chiller nameplate
Performance
Capacity500 tons (1,758 kW cooling)
RefrigerantR-134a
Chilled water54 → 44 °F at 1,200 gpm
Condenser water85 → 95 °F at 1,500 gpm
Full-load efficiency0.583 kW/ton
IPLV0.405 kW/ton
Second-law efficiency70% at full load
Machine
CompressorSingle-stage centrifugal, variable inlet guide vanes
Motor450 hp, 4,160 V, 3-phase
Evaporator approach4 °F
Condenser approach3 °F clean
TubesEnhanced copper, 2-pass

The physics

The equations behind every curve on this page.

Carnot limit

COP = T_evap / (T_cond − T_evap)

The smaller the temperature gap, the less work per ton.

Real machine

COP = η_II · COP_carnot

Second-law efficiency 70% at full load.

kW per ton

kW/ton = 3.517 / COP

0.583 kW/ton at full load, IPLV 0.405.

IPLV

0.01·A + 0.42·B + 0.45·C + 0.12·D

Weighted average over four load points.

Load and lift

Efficiency changes with how hard the chiller is working and how warm the condenser water is.

Efficiency across the load range

Condenser water follows the rating points: 85, 75, 65, 65 °F

Efficiency across the load range0.200.300.400.500.600.700.800.9001020304050607080901000.5830.4670.3630.385Load (% of 500 tons)Efficiency (kW per ton)
  • kW per ton at rating conditions
Full load
0.583 kW/ton
IPLV
0.405 kW/ton

A chiller spends most hours at part load, so the part-load points carry most of the weight in the yearly average.

IPLV = 0.01·A + 0.42·B + 0.45·C + 0.12·D

Condenser water temperature sets the lift

Condenser water temperature sets the lift0.30.40.50.60.70.80.95560657075808590Entering condenser water (°F)Efficiency (kW per ton)
  • 100% load
  • 75% load
  • 50% load

The compressor works against the temperature gap between the evaporator and the condenser. A cooler condenser water supply shrinks the gap and the bill.

COP ≈ η_II · T_evap / (T_cond − T_evap)

Fouling

The approach temperature is the cleanest fouling signal. It moves before the efficiency does.

Fouled condenser tubes

75% load, 75 °F entering condenser water

Fouled condenser tubes0.400.450.500.550.600.650.702468101214Clean 0.467Fouled 0.539Condenser approach (°F)Efficiency (kW per ton)
  • kW per ton
Extra power
27 kW, about $8,899 a year

Scale on the tubes forces a hotter refrigerant temperature to push the same heat out. The approach temperature shows it before the efficiency does.

approach = T_refrigerant,sat − T_condenser water,leaving

Failure modes

What breaks, what it looks like, what the twin does about it.

Failure modeThe physicsSignals that show itHow the twin catches it
Condenser tube foulingScale adds thermal resistance. Refrigerant condenses hotter.Condenser approach up. kW/ton up at the same load and tower water.Expected approach for the current flow and load. The gap is the fouling.
Evaporator foulingFilm on the tubes lowers the saturation temperature.Evaporator approach up. Lower suction pressure.Same approach check on the cold side.
Refrigerant underchargeLess liquid reaches the expansion valve.Rising evaporator approach. Capacity loss. Subcooling falls.Energy balance across both heat exchangers.
Compressor bearing and gear wearBearing and mesh frequencies are set by geometry.Vibration lines. Oil temperature. Current.Tracks band energy at predicted frequencies.
Low oil pressureFilter, pump or foaming problems cut flow to the bearings.Oil pressure differential and temperature.Flags a drift before a trip.

How we catch it early

A physics twin and a PINN, working on one water-cooled centrifugal chiller.

The twin is a set of equations for this machine, tuned to its nameplate. Give it the flow, speed and conditions and it returns what every reading should be. It always gives the same answer for the same inputs.

A physics-informed neural network, or PINN, sits on top. It is trained on the plant’s own data and it is penalized whenever it breaks a physics rule. So it can only learn what the equations leave out: wear, fouling, friction. It cannot invent an answer that the machine could never produce.

  1. Step 1

    Measure

    Flow, pressure, current, temperature, vibration. Whatever the asset already has.

  2. Step 2

    Physics twin

    The equations of this machine, set to its nameplate. It says what the readings should be right now.

  3. Step 3

    Residual

    Measured minus expected. Demand, weather and speed are already taken out.

  4. Step 4

    PINN

    A small neural network that learns the cause of the gap, under the physics rules.

  5. Step 5

    Finding

    A named cause, a date, and the kWh or hours at stake. An engineer reviews it.

loss = (measured − predicted)² + λ · (physics residual)²

The second term is the rulebook. It is zero when the network obeys the equations.

Why this beats black-box AI

A black-box model learns patterns from history. It needs examples of each failure, and it goes quiet when the pump runs at a point it has not seen. The twin starts from physics, so it works on day one. The PINN adds what physics cannot know about this particular machine.

That is also what makes the savings countable. The baseline is a calculation, not a guess, so the gap between baseline and meter is a number a customer can check.

What the twin checks on this asset

  • kW per ton against the twin at each load
  • Condenser and evaporator approach
  • Lift and condenser water setpoint
  • Energy balance across the evaporator
Fixed alarmBlack-box AITwin + PINN
Needs failure history to learnNoYes, lotsNo
Says what is wrongNoRarelyYes, by name
Works at a flow it has never seenNoOften failsYes, the equations still hold
Puts a number on the savingNoNoYes, in kWh and dollars
Lead time on slow wearLateVariesWeeks to months
Every number can be tracedYesNoYes, to an equation

What the twin puts a number on

Energy and cost, from the equations.

Full-load efficiency

0.583 kW/ton

500 tons, 85 °F condenser water

IPLV

0.405 kW/ton

Four-point weighted average

Fouled approach, 10 °F

27 kW

$8,899 a year at 3,000 hours